Energy monitoring in building automation systems
Renewable energy and industrial monitoring
Ease of setup and integration
Biino hexibility
Voltage Inputs(V1,V2,V3,VN) | |
| Standard Un | 240VLN/415VLL |
| Range | 10V to 1.2Un |
| Start Voltage | 10V |
| Overload | 1.2xUn continuous, 2xUn for 10s |
| Burden | <0.05VA/phase |
| Frequency | 45-65Hz |
| Voltage Inputs(VN,VG) | |
| Range | 0~5V |
Current Inputs(I11,I12,I21,I22,I31,I32) | |
| In Primary | 5A/100A/200A/250A/400A/800A |
| In Secondary | 1.667mA for 5A 40mA for 100A/200A/250A/400A/800 |
| Range | 0.4% to 100% In Primary |
| Starting Current | 0.004 In Primary |
| Solid Core CT Range 100A Molded Case CT (3-Ø) 250A Solid Core CT (1-Ø) 400A Solid Core CT (1-Ø) 800A Solid Core CT (1-Ø | 0.4~100A 1~250A 1.6~400A 3.2~800A |
| Split Core CT Range 5A SCCT (1-phase) 100ASCCT(1-phase) 200ASCCT(1-phase) 400ASCCT(1-phase) 800ASCCT(1-phase) | 0.02~5A 0.4~100A 0.8~200A 1.4~400A 3.2~800A |
Burden | <0.3 VA per phase @In |
| Overload | 1.0xIn Primary (continuous) |
Power Supply(L+,N-) | |
Standard | 95-250VAC/VDC ± 10%, 47-440 Hz |
Optional | 20-60VDC |
| Burden | <2W |
Digital Inputs | |
Type | 48VDC External Excitation |
Digital Outputs | |
Type | Form A Mechanical Relay |
Loading | 5A@250VAC or 30VDC |
| Analog Input | |
| Type | 0-20/4-20mA |
| Overload | 24mA maximum |
Installation Torque | |
Power Supply/Voltage Input | 0.8N.m |
| AI /RS485 | 0.2N.m |
| DO /DI | 0.4N.m |
Environmental Conditions | |
Operating Temp. | -25 °C to + 70°C |
Storage Temp. | -40 °C to + 85°C |
Humidity | 5% to 95% non-condensing |
Atmospheric Pressure | 70 kPa to 106 kPa |
Altitude | ≤3000m |
Mechanical Characteristics | |
Unit Dimensions | 126x90x65mm |
IP Rating | IP50 |
Communications | |
Protocol | Modbus RTU, |
RS-485 Port | 2 |
Features Summary | |
Display (Backlit) | Dot-Matrix LCD (Backlit) |
Type of Measurement | ULN per Phase &Avg. ULL per Phase&Avg. Current per Phase &Avg. Neutral Current (Meas./Calc.) Frequency kW per Phase & Total kvar per Phase & Total kVA per Phase& Total PF per Phase& Total kWh lmport/Export kvarh Import/Export kVAh Total |
Power Quality | THD Voltage & Current TOHD Voltage & Current TEHD Voltage & Current 2nd-31st Harmonics K-Factor Voltage/Current Unbalance |
Battery-backed Real-time Clock | √ |
Demands | Present Demands and Max.Demands for This Month & Last Month |
Alarm Setpoints | √ |
Logs | |
Max./Min.Log | 24 Months |
Freeze Logs(Optional) | 1000 Daily Freeze Logs, 24 Monthly Freeze Logs |
Data Recorder(Optional) | 1 Data Recorder Max. Recording Depth @ 5000 record s |
SOE Log | 512 entries |
On-board Log Memory | 4MB |
| Parameters | Accuracy | Resolution |
|---|---|---|
| Voltage | ±0.5% | 0.01V |
| Current | ±0.5% | 0.001A |
| Phase Angle | ±1° | 0.1° |
| kW,kvar,kVA | ±1.0% | 0.001kx |
| kWh | IEC 62053-21:2003 Class 1 | 0.01kXh |
| kvarh | IEC 62053-24:2014 Class 1 | 0.01kvarh |
| AI | ±1.0% | - |
| PF | ±0.5% | 0.001 |
| Frequency | ±0.02Hz | 0.01Hz |
| THD | IEC 61000-4-7 Class B | 0.1% |
| Voltage Unbalance | ±0.2% | 0.01% |
| Current Unbalance | ±1.0% | 0.01% |
Safety Requirements | |
|---|---|
| CE LVD 2014/35/EU | EN 61010-1: 2010 EN 61010-2-030: 2010 |
| Electrical Safety in Low Voltage Distribution Systems up to 1000Vac and 1500Vdc | IEC 61557-12:2008 |
| Insulation AC Voltage: 2kV@1 minute Insulation Resistance: >100MΩ Impulse Voltage: 6kV,1.2/50µs | IEC 60255-5-2000 |
Electromagnetic Compatibility CE EMC Directive 2014/30/EU(EN 61326:2013) | |
Immunity Tests | |
| Electrostatic Discharge | EN 61000-4-2:2009 |
| Radiated Fields | EN 61000-4-3:2006+A1:2008+A2:2010 |
| Fast Transients | EN 61000-4-4:2012 |
| Surges | EN 61000-4-5:2006 |
| Conducted Disturbances | EN 61000-4-6:2009 |
| Magnetic Fields | EN 61000-4-8:2010 |
| Oscillatory Waves | EN 61000-4-12:2006 |
Emission Tests | |
| Limits and Methods of Measurement of Electromagnetic Disturbance Characteristics of Industrial,Scientific and Medical(ISM) Radio-Frequency Equipment | EN 55011:2009 + A1:2010 (CISPR11) |
| Limits and methods of measurement of radio disturbance characteristics of information technology equipment | EN 55022:2010 + AC:2011 (CISPR22) |
| Limits for Harmonic Current Emissions for Equipment with Rated Current≤16A | EN 61000-3-2:2014 |
| Limitation of Voltage Fluctuations and Flicker in Low-Voltage Supply Systems for Equipment with Rated Current≤16A | EN 61000-3-3:2013 |
| Emission Standard for Residential, Commercial and Light-Industrial Environments | EN 61000-6-4:2007+A1:2011 |
| Electromagnetic Emission Tests for Measuring Relays and Protection Equipment | EN 61000-4-12:2006 |
Mechanical Tests | |
| Vibration Test Response Endurance | IEC 62052-11:2003 Level I IEC 62052-11:2003 Level I |
| Shock Test Response Endurance | IEC 62052-11:2003 Level I IEC 62052-11:2003 Level I |
| Bump Test | IEC 62052-11:2003 Level I |
Wiring Mode | |
|---|---|
| 3P4W | 3P4W without PTs & with VG 3P4W without PTs & VG 3P4W with VG and PTs |
| 3P3W | 3-Phase 3-Wire without PTs 3-Phase 3-Wire with PTs |
| 1P2W | 1-Phase 2-Wire Wiring with VG 1-Phase 2-Wire Wiring without VG |